Technical Manual 
WDGA with CANopen Interface 
5 - General information about CAN 
© Wachendorff Automation GmbH & Co. KG 
17 
Operational 
Object 
Communication enabled 
SDO 
yes 
PDO 
yes 
NMT 
yes 
SYNC 
yes 
EMCY 
yes 
Heartbeat 
yes 
Device is in operational status and can send and receive PDOs. 
Table 5.5: Available communication – Operational 
Stopped 
Object 
Communication enabled 
SDO 
no 
PDO 
no 
NMT 
yes 
SYNC 
no 
EMCY 
no 
Heartbeat 
yes 
The communication is almost completely disabled. 
The device only reacts on NMT commands (e.g. start node). 
Table 5.6: Available communication – Stopped 
5.5  Heartbeat and Node-Guarding 
There are two possible ways to supervise the operational availability of a CAN node 
during operation. 
•  Heartbeat 
•  Node-Guarding 
The  heartbeat  protocol  is  independent  from  the  master.  It  is  the  recommended 
mechanism. The device sends autonomous and cyclic a "life" message. 
•  Wachendorff Automation recommends the use of the 
heartbeat protocol. 