User manual - MA964802 21
8
.
7
Digital input 3 functions
The
Modbus remote display MA964802 integrates a further digital input
associated to the function selected by the
Digital input 3 -> Input function
parameter
Select variab.
: the digital input allows you to enable or con rm editing of
the variables on the currently displayed screen. This function is useful when
using the panel encoder to edit values by means of digital inputs 1 and 2. In
this case, pushing the encoder connects this input.
By setting
Digital input 3
in the
Alarm x
->
Alarm type
parameters, the relative
relays activate simultaneously with the digital input. The function set in the
Digital input 3 -> Input function
parameter continues to work.
By setting
Digital input 3
in the
Variable x
->
Data source
parameters, the
corresponding variable will take on the value 0 or 1 depending on the status
of the digital input. The function set in the
Digital input 3 -> Input function
parameter continues to work.
8
.8 Alarm triggering modes
MA964802
implements various alarm modes, described below.
8.8.a Absolute alarm (“Absolute” selection)
1
Alarm Spv
Pv
On On
Hysteresis
par. > 0
Time
Alarm
output
Absolute alarm and hysteresis value
greater than “0” (Par.58
Hysteresis
>
0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarm 2.