FUNCTIONAL DESCRIPTION/SYSTEMS OVERVIEW
FlexVent™ has three 165 °F fusible links arranged in a series under the Vent Hood and behind the Particulate
Filters. If any link is actuated, the Fire Suppression System is activated. In the event the Fire Suppression
System is activated (automatically or manually), power to the cooking appliance(s) and fan motor is terminated.
Negative pressure within the plenum is monitored with two pressure switches. One terminates power to the
unit if the pressure is too high (e.g., filtration is obstructed), the other terminates power if pressure is too low
(e.g., filtration wrong or missing, fan not operating properly).
Item System
Description
Components & Specs Function
A Cooking
Station
• Adjustable-mount shelf
18 ⁄”D X 35 ⁄” W
• Holds up to three ap-
proved appliances no
more than 80 lbs each or
120 lbs total.
B Ventilation
Control and
Interlock
System
• Touchscreen User Interface
(Vollrath® logo glows when unit has power)
• Pressure Control Box, power relay & 30-amp
circuit breaker
• Integral Interlock System
• Controls function, dis-
plays status
• Activates lighting option
• Cuts Cooking Station
outlet power if there is a
pressure error or fire.
C Recirculating
Filtration
Ductless Hood
Assembly
• Hood, plenum, and ductwork — stainless steel
• Bae type grease filters — stainless steel (2)
Item # 352035-2, UL File R37947*
• Activated carbon particulate air filters (2) Item #
352010-1*
• Recirculating fan
• Fire Damper
• Captures grease
• Filters grease particles*
• Filters small particles and
light odors*
• Interlock
D UL 300
Automated
Fire Sup-
pression
System**
Pre-plumbed
for ANSUL
R-102 wet
chemical
suppression
system
• Piping
• Plenum discharge nozzles 1W
• Fire Detection Links 165 °F, Fusible (3)
• Appliance Discharge Nozzles 1W***
• 1 ⁄ gal ANSULEX low pH Liquid Fire Suppressant
• Manual Pull
• Interlock Control Box supplied with power relay
and 30-amp circuit breaker
• Automatic and manual fire
suppression
• Distribution of suppres-
sant inside plenum, be-
hind grease filters, and for
cooking appliances
• Interlock cuts power to
unit and cooking appli-
ances if fire is detected
*Vollrath specified filters must be used as replacements to optimize performance.
**The Fire Suppression System, field installation, set-up, testing and final charging shall be provided by
an authorized ANSUL Distributor/Dealer and is the sole responsibility of the purchaser.
***Do not adjust nozzle angles; they are factory set for optimal fire suppression.