4.2 Monobloc Leaving Water Temperature (LWT) Selection
The recommended design LTW ranges for different types of heat emitter are:
For floor heating: 30 to 35⁰C
For fan coil units: 30 to 45⁰C
For low temperature radiators: 40 to 50⁰C
4.3 Optimizing System Design
To get the most comfort with the lowest energy consumption with M thermal, it is important to take account of the
following considerations:
Choose heat emitters that allow the heat pump system to operate at as low a hot water temperature as possible
whilst still providing sufficient heating.
Make sure the correct weather dependency curve is selected to match the installation environment (building
structure, climate) as well as ender user’s demands.
Connecting room thermostats (field supplied) to the hydronic system helps prevent excessive space heating by
stopping the outdoor unit and circulator pump when the room temperature is above the thermostat set point.
4.4 Tank back up heater notice
Heat pump will stop when T5(tank temperature) has reached the minimum of both T5S(tank setting temperature) and
T5stop (highest tank temperature which can be reached under certain ambient temperature with heat pump only) and
lasted for 5s. The value of T5stop is shown as below.
If T5S is higher than T5stop, then T5S can not be reached with heat pump only. In this case, tank back up heater is needed
in order to reach T5S.
T5stop value:
Ambient temperature(
ć
)
< -20
-20~15
-15~-10
-10~-5
-5~0
0~5
5~10
T5stop(
ć
)
35
40
45
48
52
55
56
Ambient temperature(
ć
)
10~15
15~20
20~25
25~30
35~40
40~65
40~65
T5stop(
ć
)
57
56
55
52
50
48
45