Vivax HPM-28CH84AERIs R32-1H3 handleiding

112 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 24 van 112
ENG VIVAX
24
Outdoor unit model name
HPM-41CH120AERIs R32-3H9
HPM-48CH140AERIs R32-3H9
HPM-53CH155AERIs R32-3H9
Power supply V/Ph/Hz 380-415/3/50
Heating A7W35
Capacity
kW 12.1 14.5 15.9
Rated input
kW 2.44 3.15 3.53
COP
4.95 4.60 4.50
Heating A7W45
Capacity
kW 12.3 14.1 16.0
Rated input
kW 3.32 3.92 4.57
COP
3.70 3.60 3.50
Heating A7W55
Capacity
kW 11.9 13.8 16.0
Rated input
kW 3.90 4.68 5.61
COP
3.05 2.95 2.85
Heating A
-7W35
Capacity
kW 10.00 12.00 13.10
Rated input
kW 3.33 4.21 4.85
COP
3.00 2.85 2.70
Heating A
-7W55
Capacity
kW 9.80 11.00 12.50
Rated input
kW 4.78 5.37 6.25
COP
2.05 2.05 2.00
Cooling A35W18
Capacity
kW 12.00 13.50 14.2
Rated input
kW 3.04 3.74 3.94
EER
3.95 3.61 3.61
Cooling A35W7
Capacity
kW 11.5 12.4 14.0
Rated input
kW 4.18 4.96 5.60
EER
2.75 2.50 2.50
Seasonal space heating
energy efficiency class
Water outlet at 35C
A+++
Water outlet at 55C
A++
SCOP
Warmer climate
35C 6.47 6.57 6.28
55C 4.42 4.49 4.47
Average climate
35C 4.81 4.72 4.62
55C 3.45 3.47 3.41
Colder climate
35C 4.08 4.07 4.02
55C 3.02 3.05 3.12
SEER
Water outlet
7C 4.90 4.85 4.67
18C 7.07 6.89 6.70
Sound power Level
2
dB 65 65 68
Rated water flow
m
3
/h 2.08 2.49 2.73
Water flow range
m
3
/h 0.7~2.5 0.7~2.75 0.7~3.0
Internal water volume
L 3.83-8.63 3.83-8.63 3.83-8.63
Backup electric heater
Capacity
kW 9 9 9
Power supply
V/Ph/Hz
380-415/3/50
380-415/3/50
380-415/3/50
Compressor
Type
Twin rotary
Outdoor fan
Motor type
DC fan
Number of fans
1
Air side heat exchanger
Finned tube
Refrigerant
R32 1.75kg
Unit dimension (W×H×D)
mm 1385×865×523

Bekijk gratis de handleiding van Vivax HPM-28CH84AERIs R32-1H3, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkVivax
ModelHPM-28CH84AERIs R32-1H3
CategorieAirco
TaalNederlands
Grootte28688 MB