5.3 Application 3
5.3.1 Group control
Figure 1-5.5: Application 3- Parallel system control
Legend
1.1
Master unit
11.3
Coil 2: heat exchanger for heat pump
1.2…n
Slave unit
12
Filter(Accessory)
2
User interface
13
Check valve (Field supply)
3
SV1: 3-way valve(Field supply)
14
Shut-off valve(Field supply)
4
Balance tank(Field supply)
17
Tap water inlet pipe(Field supply)
4.1
Automatic bleed valve
18
Hot water tap(Field supply)
4.2
Drainage valve
19
Collector/Distributor(Field supply)
4.3
Tbt1: Balance tank upper temperature sensor(optional)
20
Bypass valve(Field supply)
4.5
Filling valve
23
Mixing station(Field supply)
5
P_O: Outside circulation pump (Field supply)
23.1
SV3: Mixing valve(Field supply)
6
P_S: Solar pump(Field supply)
23.2
P_C: Zone B circulation pump(Field supply)
6.1
Tsolar: Solar temperature sensor(Optional)
24
Automatic bleed valve(Field supply)
6.2
Solar panel (Field supply)
25
Water manometer(Field supply)
7
P_D: DHW pipe pump(Field supply)
Tw2
Zone B water flow temperature sensor(Optional)
8
T5: Domestic water tank temperature sensor(Accessory)
RAD 1…n
Radiator(Field supply)
9
Expansion vessel(Field supply)
FHL 1…n
Floor heating loop(Field supply)
10
T1: Total water flow temperature sensor(Optional)
K
Contactor(Field supply)
11
Domestic water tank(Field supply)
ZONE 1
The space operate cooling or heating mode
11.1
TBH: Domestic water tank heater
ZONE 2
The space operate heating mode
11.2
Coil 1: heat exchanger for heat pump
AHS
Auxiliary heat source(Field supply)
Notes:
1. The example is just for application illustration; please confirm the exact installation method according to the installation manual.
Modularity is perfect when an extension of capacity becomes required as the building cooling/heating demand evolves. 6
units can be controlled in group. The group control system can control and view the operation of the entire system only by
connecting the master to the wire controller. If the DHW function is required, the water tank can only be connected to the
master unit water circuit through a three-way valve, and controlled by the master unit. If AHS is needed, it can only be
connected to the master waterway and controlled by the master unit. The Tbt1 temperature sensor must be installed in
the parallel system (otherwise unit cannot be started). If the balance tank is too large, Tbt2 needs to be added in order to
improve the control accuracy. Tbt2 is set in the lower part of the balance tank. The water inlet and outlet pipe joints of