BUILDING AUTOMATION
Parameter “If bus recovery, position is”
The parameter is used to set the position where shutter moves, after the output on bus recovery. Options:
Unchange
Up
Down
Stop
If the option “Unchange” is set, the output contacts remain in their current position.
If the option “up” is set, the Shutter is moved to the top after bus voltage recovery.
If the option “down” is set, the Shutter is moved to the bottom after bus voltage recovery.
If the option “stop” is set, if the shutter is moving, it will be stopped after bus recovery.
All output contacts are opened after bus voltage recovery.
Note: If after programming or bus voltage recovery, the Shutter actuator does not detect the current position of the Shutter. The communication ob-
jects “ position status0…100%” and “slat status 0…100%” have the default value “50%” and are not sent on the bus.Telegram will be sent to the bus
after assure the position.
If after programming or bus voltage recovery a defined position of the Shutter is required for the first time, it is first of all raised to the top or dropped
to the bottom (toward near the target location moving) to determine the current position and then into the target position. Only the Shutter finish a full
running can confirm position.
Parameter “If bus failure, position is”
The parameter is used to set the position where shutter moves after on bus voltage failure. Options:
Unchange
Up
Down
Stop
If the option “Unchange” is set, the output contacts remain in their current position.
If the option “up” is set, the Shutter is moved to the top after bus voltage failure.
If the option “down” is set, the Shutter is moved to the bottom after bus voltage failure.
If the option “stop” is set, if the shutter is moving, it will be stopped after bus voltage failure.
Note: Before the power-down, the curtain is running, and in power-down it is required to perform a reverse operation, then this operation will not be
implemented, but to maintain the current running state.
Parameter “Final position after tuning procedure”
This parameter specifies how the Shutter actuator behaves after a reference movement. Options:
Disableb
Botton up/down
Move to previous position
If “Disable” is selected, the reference movement is deactivated;
If “Botton up/down” is selected, the object “reference movement” receives a telegram “0”, the Shutter is moved to the top; the object receives a telegram “1”,
the Shutter is moved to the bottom.
If “Move to previous position” is selected, the object receives a telegram “1”, the Shutter is moved to the bottom, then back to its original position; the object
receives a telegram “0”, the Shutter is moved to the top, then back to its original position.
During the movement of shutter, the shutter actuator continually determines the current position of the shutter as well as the angle position of the slat using the
duration of individual movements. Over longer periods, slight inaccuracies may occur when determining the position due to temperature variations and aging
processes. Therefore the Shutter actuator uses the upper and lower limit positions to clearly define the current position of the Shutter. Each time that the Shutter
is in the upper or lower limit position, the position is updated in the memory of the Shutter actuator.
If the limit positions have not been reached during normal operation, a reference movement can be triggered via a bus telegram to move the Shutter right to the
top or right to the bottom. Depending on the parameter settings, the Shutter either remains in the reference position after the reference movement or moves back
into the saved position.
Parameter setting description in the ETS