BUILDING AUTOMATION
• Parameter “Valve position during fault”
This parameter is set in the valve position in fault mode, the valve will switch action according to the PWM cycle. Options:
0%[Closed]
10%[26]
100%[Open]
Unchange
For example, 20%, the PWM cycle time as 100s(1min40s), then the cycle time of valve switching behavior is on for 20s, off for 80s.
If select “Unchange”, the valve position does not change.
• Parameter “Send object “Report fault” is”
This parameter sets whether to send a telegram to report a fault in fault mode. If enabled, when the device does not receive a control value during the monitoring time,
an error report is sent, and this output channel performs a dynamic action in fault mode until it is interrupted by another operation. When the control value is received
again, the monitoring time starts again. Options:
Disable
Enable
When select ”Enable”, object ”Report fault” will be active, when object ”Report fault” is “1”, indicates that this output channel enter fault mode,when”0” indicate this
output channel is not fault.
Parameter “Function of forced operation is”
This parameter setting whether to enable function of forced operation. Options:
Disable
Enable
• Parameter “Valve position during forced operation”
This parameter setting the valve position during forced operation. Options:
0%[Closed]
10%[26]
100%[Open]
Unchange
If option “Unchange”, the valve position does not change.
At the end of the forced operation mode, the valve output state will return to the previous operation. For example, if the valve position under forced operation is 40%
and the previous operation is 60%, then the valve output state will return to the valve position of 60% after exiting the forced operation.
During forced operation, monitoring time of the monitor is still continuous, and when the monitoring time is up, an error report will be sent, but the action under the
fault cannot be executed, and it can only be executed after the forced operation is exited. During the forced operation, the received control telegram of common
operation will be recorded.
The priority for various operations of heating actuator:
Initialization (After the parameter download is completed) Manual operation (Long press the manual button to switch to manual operation, and the but-
ton of the channel has operation) force operation general or fault operation
Apply to the following points:
1. During the manual operation, the received control value and force operation command are invalid, but the fault monitoring is continue, and the control
value can also reset fault monitoring period. After exiting manual operation, it will perform action according to the fault status, if no fault, it will maintain
until a new control command received. If there is a force operation before, then return to the status of force operation.
Exit the force, it will perform action according to the current control value or the fault status.
2. At the end of the forced operation mode, the status of switch output will return to the current control value or the fault status. During force operation,
the received control telegram of general operation will be recorded.