6.1.3 Connection of the power supply
line
Earth cable should be about 10mm longer
than the other two, so that it will not be
disconnected accidentally if pulled.
All signal cables must be grouped together
by means of a strap.
Connect the cables as shown in figure.
IN
OUT
a
24Vac
24Vac
a
N
L
Fig. 3 Standard box.
N
L
a
IN
Fig. 4 UL certified box.
Use the supplied gaskets for cables with
reduced diameters: From 3mm a 6mm.
Fig. 5
6.1.4 Connecting the light sensitive
switch for the LED illuminator
Connect the Day/Night (J5) output identified by
STATUS (+) to the alarm input (refer to the P&T
manual).
Connect the second Day/Night (J5) output identified
by STATUS to the alarms common terminal of the P&T.
6.1.5 Connector installation
The operation is only to be carried out with
UL certied versions.
Access the lower part of the Pan & Tilt base.
Disassemble the highlighted cable gland to replace
it with the provided connector, taking care not to
damage the fixing nut.
Fig. 6