Vevor EM5500-48L handleiding

352 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 33 van 352
- 31 -
Set Low DC cut-off voltage ≥discharging protection voltage of BMS+2V.
29
Low DC cut-off
voltage
default setting: 42.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 20.0V to 27.0V for 24v model
and 40.0V to 54.0V for 48v model. The setting value must be less than
the value of program12. Increment of each click is 0.1V.Low DC
cut-off voltage will be fixed to setting value no matter what percentage
of load is connected.
Set Max charging current which must be less than the Max charging current
of BMS.
02
Maximum charging
current: To configure
total charging current for
solar and utility
chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A (default)
If selected, acceptable charging
current range will be within 1-
Max.
charging current of SPEC but it
shouldn’t be less than the AC
charging current program 11
Setting voltage point back to utility source when selecting SBU priority” or
“Solar first” in program 01.The setting value must be ≥Low DC cut-off
voltage+1Vor else the inverter will have a warning as battery voltage low.
12
Setting voltage point
back to utility source
when selecting “SBU
priority” or “Solar first in
program 01.
Available options in 48V models: 46V (default)
Available options in 24V models: 23V (default)
Remark:
you’d better to finish setting without turn on the inverter(just let the LCD show, no
output); when you finish setting, please restart the inverter.

Bekijk gratis de handleiding van Vevor EM5500-48L, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkVevor
ModelEM5500-48L
CategorieNiet gecategoriseerd
TaalNederlands
Grootte56647 MB