Set Low DC cut-off voltage ≥discharging protection voltage of BMS+2V.
29
Low DC cut-off
voltage
default setting: 42.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 20.0V to 27.0V for 24v model
and 40.0V to 54.0V for 48v model. The setting value must be less than
the value of program12. Increment of each click is 0.1V.Low DC
cut-off voltage will be fixed to setting value no matter what percentage
of load is connected.
Set Max charging current which must be less than the Max charging current
of BMS.
02
Maximum charging
current: To configure
total charging current for
solar and utility
chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A (default)
If selected, acceptable charging
current range will be within 1-
Max.
charging current of SPEC ,but it
shouldn’t be less than the AC
charging current ( program 11)
Setting voltage point back to utility source when selecting “SBU priority” or
“Solar first” in program 01.The setting value must be ≥Low DC cut-off
voltage+1V,or else the inverter will have a warning as battery voltage low.
12
Setting voltage point
back to utility source
when selecting “SBU
priority” or “Solar first” in
program 01.
Available options in 48V models: 46V (default)
Available options in 24V models: 23V (default)
Remark:
you’d better to finish setting without turn on the inverter(just let the LCD show, no
output); when you finish setting, please restart the inverter.