9 Maintenance
Warning! Improper decommissioning may cause damage to the equipment and/or
battery inverter.
Before maintenance, ensure that OHL-233 is decommissioned according to relevant provisions.
Note: All maintenance work shall comply with local applicable regulations and standards.
The USB-CAN port of OHL has the functions of upgrading firmware and recording battery data, which
can be used as an auxiliary tool.
To ensure safe operation, all plug connections must be checked. If necessary, relevant operators
shall press them back into place at least once a year.
The following inspection or maintenance must be carried out once a year:
• General visual inspection
• Check all tightened electrical connections. Check the tightening torque according to the values
in the following table. Loose connections must be retightened to the specified torque.
Connection mode
Tightening torque
high-voltage BMS box grounding
4.5Nm
Fixing the lug of the high-voltage BMS box
1.2Nm
Fixing the lug of the battery module
1.2Nm
• Using the monitoring software, check whether the SoC, SoH, battery voltage and temperature
of the battery module are abnormal.
• Shut down and restart OHL-233 once a year.
Note: If the system is installed in a polluted environment, maintenance and cleaning must be
carried out at short intervals.
Note: Clean the battery rack with a dry-cleaning cloth. Ensure that no moisture comes into
contact with the battery connections. Do not use solvents.