Door lock
maintenance
Check whether the door locks etc. of each door panel of the energy
storage system are normal and in good condition. If necessary,
lubricate the door lock holes appropriately.
Every half year once
Liquid cooling
unit
maintenance
Check whether the power cables and communication cables are
loose, and whether the operation and communication are abnormal.
Check whether there is no abnormality in appearance, fastening and
grounding.
Check whether the fan and condenser work normally, whether there
is any foreign matter blocked at the air outlet, whether there is any
abnormal vibration during normal operation.
4. Check whether there is leakage in the water circuit system;
whether there is leakage in the connectors and whether there is
cracking and deformation in the hoses.
5. Check whether the balloon of the expansion tank is damaged
(press the thimble at the inflatable place by hand, if the water
continues to come out, then it is damaged), and the balloon needs to
be replaced.
6. 1) Acidity and alkalinity test: check the PH value of the coolant,
need to prepare PH test paper to test the PH value of the coolant, if
the PH value is lower than 7, then the coolant needs to be replaced;
(recommended to test once a
year).
2) When the service life of the coolant reaches 10 years, it also needs
to be replaced.
The above 1) and 2) replacement conditions are based on the
conditions achieved first. Please contact the manufacturer for
coolant recharge or replacement.
Note: If there is any abnormality in the fan, it needs to be replaced in
time to avoid temperature problems, which may lead to failure of the
energy storage system.
There is no need to power down the liquid cooling unit when
communicating, replacing the coolant, or replenishing the coolant.
Every three months to six
months once
* The table above is only the recommended routine maintenance cycle, the actual product should be
maintained based on the specific installation and use environment. The size of the power plant, the location, and
the site environment and other factors will affect the product's routine maintenance cycle.
* If the energy storage system is installed in a harsh environment with heavy wind and sand or dense dust,
please shorten the maintenance cycle and increase the frequency of maintenance.