6.OHL’S User Interface
6.1 Main Interface
2
NO.
Description
Function
1
SOC
Display real-time SOC value of energy storage system
2
Voltage
Display real-time voltage
3
Temperature
Displays the maximum and minimum battery temperatures
4
Voltage
Displays real-time maximum and minimum cell voltages
5
Current
Display battery real-time current
6
System status
Display battery fault name (For details, see Table 5-2)
6.2Alarm description and processing
When protection mode is activated or system failure occurred, the alarm signal will be given
through the system status on the LCD. The network management can query the specific alarm categories.
If the fault such as single cell over voltage, charging over-current, under-voltage protection,
high-temp protection and other abnormalities which affects the output, please deal with it
according to Table 5-2.
Table 5-2 Main alarm and Protection
Statue
Alarm category
system status
Processing
Charge state
Over-current
Over-current during slow charging
Stop charging and find
out the cause of the
trouble
Over-voltage
Cell voltage too high in charge
Stop charging
High temp
Temperature too high in charge
Stop charging
Low temp
Temperature too low in charge
Stop charging