energy storage system.
Generally, the energy storage system can operate normally after drying and ventilating twice.
* If the product needs to be transported again, please strictly pack it before loading it for
transporting.
3.3 Selection of Installation Site
When choosing an installation site, observe the following principles at least.
* The site where the energy storage system is placed should be solid and flat, well-drained, free of
obstacles or protrusions, and avoid sites with existing underground utilities.
* The site should be open or solid enough above the site, with no risk of water or foreign objects
falling on it.
* The surrounding environment of installation should be dry and well ventilated, and there should
be no flammable, explosive or corrosive substances. Keep away from areas where dust, fumes,
corrosive gases and noxious gases are generated.
* Do not install the energy storage system outdoors in salt damage areas.
Salt damage areas mainly refer to coastal areas within 500m from the coast. The precipitation amount of
salt spray varies greatly depending on the characteristics of seawater in the neighboring sea, sea breeze,
precipitation, air humidity, terrain and forest cover.
* Do not install the energy storage system in locations accessible to children.
* The installation location needs to meet the necessary traffic conditions and have a reliable fire
protection system.
* The energy storage system should be installed at a distance of no less than 12m from residential
buildings and greater than 30.5m from crowded places such as schools and hospitals.
* The distance between the energy storage system and the production building must meet local
fire codes or standards.
− The safety distance between the energy storage system and the Class A production building
should not be less than 12m.
− The safety distance between the energy storage system and the Class B production building
shall not be less than 10m.
− The safety distance between the energy storage system and the production buildings of class C,
D and E that meet the fire resistance rating of not less than grade II shall not be less than 10m.
− If the outer walls of two adjacent buildings are non-burning and there are no door or window
openings or exposed burning eaves, the fire separation distance can be reduced by 25% according to
the safety distance corresponding to each type of production building.
− If the safety distance of production buildings does not meet the requirements, a protective wall
with a fire resistance of at least 3 hours must be equipped for protection. The protection spacing is not
limited, and the length and height of the firewall should exceed the outer perimeter of the energy