Heating Input Consumption@Tu=10
kW
2.35
Self-cycling Mode(Single pump operation)
Consumption
kW
0.25
Max. Power Consumption
kW
3.60
Power Supply
Rated Operating Voltage
V, Hz
220~240V 50/60Hz
Power Supply Range
V, Hz
220±15%,50/60±3Hz
Max. Operating Current
A
19.2
2.3.3 Coolant Specifications
Coolant50% ethylene glycol aqueous solution.
The specifications of the coolant used in the air-cooled chiller must meet the requirements of Table
2-6.
Table 2-6 Coolant specifications
Parameter
Value
PH
(7) 7.5–8.5
Conductivity
200–3000 μS/cm
Evaporation residue
< 500 mg/dm³
Sedimentary material
< 3 mg/dm³
Hardness
3–8 °dH (for German-speaking regions)
Ca + Mg
0.5–2 mmol/l (for international regions)
Bicarbonates
1–5 mmol/dm³ (60–300 mg/dm³)
Free carbon monoxide
< 10 mg/dm³
Sulfide
< 0.01 mg/dm³
Chloride
< 50 mg/dm³
Sulfate
< 250 mg/dm³
Nitrate
< 25 mg/dm³
Nitrite
< 0.1 mg/m³
CSB
< 7 mg/dm³
NH4
< 0.05 mg/dm³
Fe
< 0.1 mg/dm³
Mn
< 0.1 mg/dm³
Cu
< 0.1 mg/dm
Ethylene glycol is a substance that pollutesgroundwater, so the equipment operator must abideby the
relevant national and local regulations, andmay not discharge it at will.