① DC Breaker for battery
SUN 3.6K-SG: 150A DC breaker
SUN 5K-SG: 150A DC breaker
SUN 6K-SG: 200A DC breaker
AC Breaker for gen port
SUN 3.6K-SG: 40A AC breaker
SUN 5K-SG: 40A AC breaker
SUN 6K-SG: 40A AC breaker
2
- 19 -
SUN 3.6K-SG: 40A AC breaker
AC Breaker for backup load port
3
SUN 5K-SG: 40A AC breaker
SUN 6K-SG: 40A AC breaker
Inverter
ON
1 2
ON
1 2
Load
L N PEL N PE
L N PE
Grid
Gen
(Region:EU)
L wireCAN N wire PE wire
3.10 Typical applica�on diagram of diesel generator
Inverter
Battery pack
① DC
Breaker
Backup Load
L
N
PE
LNPE
Ground
Generator
2
3
Remotely control signal line
B HM G-V
G-S
T
ATS240V
GV/GS
(diesel generator startup signal)
relay
coil
open
contact
G V
/S
GV/GS: dry contact signal for startup the
diesel generator.
When the "GEN signal" is ac�ve, the open
contact (GV/GS) will switch on (no voltage output).
If the "Signal ISLAND MODE"is �cked, the GS
port will be the dry contact signal for startup
the diesel generator.If "Signal ISLAND MODE"
is not �cked, the GV port will be the dry contact
signal for startup the diesel generator.