- 12 -
3.4 Grid connec�on and backup load connec�on
· Before connec�ng to the grid, a separate AC breaker must be installed between the inverter
and the grid, and also between the backup load and the inverter. This will ensure the inverter
can be securely disconnected during maintenance and fully protected from over current. For
the 3.6/5/6kW model, the recommended AC breaker for backup load is 40A. For the 3.6/5/6kW
model, the recommended AC breaker for grid is 40A.
· There are three terminal blocks with "Grid" "Load"and "GEN" markings. Please do not misconnect
input and output connectors.
All wiring must be performed by a qualified personnel.It is very important for
system safety and efficient opera�on to use appropriate cable for AC input
connec�on. To reduce risk of injury, please use the proper recommended cable
as below.
Model
3.6kW
Wire Size
12AWG
Cable(mm )
2
4
Torque value(max)
1.2Nm
5kW 10AWG 6 1.2Nm
6kW 8AWG 8 1.2Nm
1. Before making Grid, load and Gen port connec�on, be sure to turn off AC breaker or
disconnector first.
2. Remove insula�on sleeve 10mm length, unscrew the bolts, insert the wires according to
polari�es indicated on the terminal block and �ghten the terminal screws. Make sure the
connec�on is complete.
Please follow below steps to implement AC input/output connec�on:
Chart 3-3 Recommended Size for AC wires