Table of alarms and signals.
When an alarm is activated, the display shows the corresponding message that flashes
alternating with the temperature; if fi tted and enabled, the buzzer and the alarm relay are also
activated.
All the alarms have automatic reset (that is, they stop when the causes are no longer present),
except for alarm ‘CHt’ which has manual reset (instrument on/off using the UP button or by
disconnecting the power supply).
Pressing the SET button mutes the buzzer, while the code displayed and the alarm relay only
go off when the causes of the alarm have been resolved.
The alarm codes are shown in the table below:
Table 7. Alarm codes table.
alarm
code
buzzer and
alarm relay
LED alarm description reset
enable alarm
parameters involved
E0 active on probe 1 error = control automatic
E1 not active on probe 1 error = defrost automatic d0=0/1/4, F0=1
E2 not active on
probe 1 error =
condenser/product
automatic A4=10
IA active on external alarm automatic A4=1, +A7
dOr active on open door alarm automatic A4=7/8, +A7
LO active on low temperature alarm automatic AL, Ad
HI active on high temperature alarm automatic AH, Ad
EE not active on unit parameter error not possible
EF not active on operating parameter error manual
Ed not active on defrost running
on first defrost
ended correctly
dP, dt, d4, A8
dF not active off defrost running automatic d6=0
cht not active on dirty condenser pre-alarm automatic A4=10
CHT active on dirty condenser alarm manual A4=10
EtC not active on clock alarm
by setting the
time
if bands active