WARNINGS:
If no button is pressed for 60 s, all the changes made to the parameters, temporarily
saved in the RAM, will be cancelled and the previous settings restored.
The dAY, hr, Min parameters are not restored, as these are saved instantly when entered.
If power is disconnected from the instrument before saving the settings (pressing the
SET button for 3 s), all the changes made to the parameters and temporarily saved will be
lost.
Table 8. Category of parameters.
Category Initial Icon Category Initial Icon
Probe parameters / - Alarm parameters A
Control parameters r - Fan parameters F
Compressor parameters c AUX output configuration parameters H1
Defrost parameters d RTC parameters -
Setting the default parameters.
WARNINGS:
running this procedure overwrites any custom parameter settings.
To reset the default parameters:
• disconnect power from the instrument;
• reconnect power while holding the SET and DOWN buttons;
• the display will show the message “CF”;
• after a few seconds the instrument starts operating with the default configuration. Any different
parameter settings will need to be updated.