local air conditioner PAC 2015 E
3. Reattach the rubber stopper to the condensate outlet.
Ensure the tight fit of the rubber stopper, for otherwise
there might be uncontrolled water leakage.
ð The Water filling levelLED(10) will go out as soon as
the condensate has been drained.
Activities required after maintenance
If you want to continue using the device:
If the device has been switched off, it cannot be switched
on for the next 3minutes.
Leave the device to rest for at least12hours if it has been
tilted by more than 45° during maintenance. During this
time, the lubricating oil can be returned to the compressor.
Wait 12hours before switching the device back on! Acting
contrary might lead to compressor damage and a
malfunctioning device.
If you do not intend to use the device for a considerable time:
Store the device according to the Transport and storage
chapter.