Toa RM-300MF handleiding

150 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 64 van 150
64
F A U L T V A
E
M
E R
G
E N C Y E V
>
F A U L T E 1
A
M
P L I F I E R
>
F A U L T E 2
A U D I
O
L I N E
< >
F A U L T E 3
C
O
M M
U N I C A T I
O
N
< >
F A U L T E 8
P
O
W
E R
< >
Failure Location: Automatic Emergency Announcement
Failure detected in the VM-3360VA or VM-3240VA’s internal
automatic emergency announcement device.
Failure Location: Fireman’s Microphone (RM-300MF)
Failure detected in the audio lines between the RM-300MF and
the VM-3360VA or VM-3240VA.
F A U L T E
M
G
R
M
2
A U D I
O
L I N E
< >
Failure detected in the emergency microphone on the
RM-300MF.
F A U L T E
M
G
R
M
1
M
I C R
O
P H
O
N E
<
Failure detected in the talk switch of the emergency microphone
on the RM-300MF.
F A U L T E
M
G
R
M
1
T A L K S
W
< >
Failure detected in communications between the VM-3360VA or
VM-3240VA and the RM-300MF.
F A U L T E
M
G
R
M
2
C
O
M M
U N I C A T I
O
N
< >
Failure detected in the Emergency Activation switch on the
RM-300MF.
F A U L T E
M
G
R
M
2
E
M
E R
G
E N C Y S
W
>
Failure detected in the power supply of the RM-300MF.
F A U L T E
M
G
R
M
1
P
O
W
E R
< >
Failure Location: VM Extension Amplifier (VM-3240E or VM-3360E)
The VM-3240E or VM-3360E has overheated or its fuse has
blown.
Failure detected in the audio lines between the VM-3360VA or
VM-3240VA and the VM-3240E or VM-3360E.
Failure detected in communications between the VM-3360VA or
VM-3240VA and the VM-3240E or VM-3360E.
Failure detected in the power supply of the VM-3240E or
VM-3360E.