Microphone announcement
Make emergency broadcasts by holding down the
emergencymicrophone’sTalkkey.
PresseithertheAll-ZoneCallkeyorOutputkeytoselecttheoutputzone.
(Ifthezoneisnotselected,emergencybroadcastsaremadeoverallzones.)
Toterminatetheemergencybroadcast,resettheemergencymodeusingoneofthefollowingmethods:
Press the Reset key on the front panel of the VM-3360VA or VM-3240VA.
• PresstheRM-300MFFireman’sMicrophone’sEmergencyResetkey.
Input a reset signal to the Emergency Control Input terminals on the rear panel of the VM-3240VA, VM-
3360VA, VM-3240E, or VM-3360E which has been assigned a reset function.
Press the Emergency Activation switch.
Normal status
Automatic emergency announcement
Press the Alert or Evacuation Announcement Start key
to broadcast the Alert or Evacuation announcement.
Microphone announcement
Make emergency broadcasts by holding down the
RM-300MF’semergencymicrophone’sTalkkey.
PresstheRM-320FFireman’sMicrophoneExtension’sZoneSelectorkeytoselecttheoutputzone.
(Ifthezoneisnotselected,broadcastsaremadeoverallzones.)
Toterminatetheemergencybroadcast,resettheemergencymodeusingoneofthefollowingmethods:
Press the Reset key on the front panel of the VM-3360VA or VM-3240VA.
• PresstheRM-300MFFireman’sMicrophone’sEmergencyResetkey.
Input a reset signal to the Emergency Control Input terminal on the rear panel of the VM-3240VA, VM-
3360VA, VM-3240E, or VM-3360E which has been assigned a reset function.
PresstheRM-300MF’sEmergencyActivationswitch.
Normal status
Automatic emergency announcement
PresstheRM-300MF’sAlertorEvacuation
Announcement Start key to broadcast the Alert or
Evacuation announcement.
AlertorEvacuationannouncementsarebroadcastoverthezonesassignedtotheEmergencyControlInputterminal.
Automatic fire alarm system is activated and an emergency control signal is input to the Emergency Control Input terminal.
Toterminatetheemergencybroadcast,resettheemergencymodeusingoneofthefollowingmethods:
Press the Reset key on the front panel of the VM-3360VA or VM-3240VA.
• PresstheRM-300MFFireman’sMicrophone’sEmergencyResetkey.
Input a reset signal to the Emergency Control Input terminal on the rear panel of the VM-3240VA, VM-3
360VA,
VM-3240E, or VM-3360E which has been assigned a reset function.
Normal status
6.4. Summary of Emergency Broadcast Procedures
6.4.1. Making emergency broadcasts from the VM-3240VA or VM-3360VA
6.4.2. Fireman’smicrophoneemergencybroadcasts
6.4.3. Making automatic emergency announcements using the control signal input