Step 2. The Alert or Evacuation announcement is broadcast over the zone(s) assigned to the Emergency
Control Input terminals. The Emergency indicator ashes red, the buzzer sounds and the Alert or
Evacuation Announcement indicator lights red. At the same time, the Output indicator corresponding
tothesetbroadcastzone(s)lights.
Step 1. AnemergencycontrolsignalisinputtotheEmergencyControlInputterminalswhenanautomaticre
alarm system is activated.
Emergency control input terminals
Note:
This figure represents the VM-3240VA/3360VA.
[VM-3240VA/3360VA/3240E/3360E]
Output indicator
Emergency indicator
Alert Announcement indicatorEvacuation
Announcement
indicator
Buzzer
[VM-3240VA/3360VA]
MakesettingssothattheAlertorEvacuationannouncementtobebroadcastoverthedesignatedzone(s)
when the emergency control input terminal of the VM-3240VA, VM-3360VA, VM-3240E, or VM-3360E is
activated. (For more information, refer to "Emergency Control Input Settings" in "Event Settings" in the
separate software instruction manual.)
Note
Assigning a function to stop the Alert or Evacuation message announcements to the emergency
control input terminals allows these announcements being broadcast to be stopped. This function can
beusedonlywhenalltheversionsofVM-3000VArmware,VM-3000Ermware,andVM-3000Setting
Software are 2.00 or later.
Use the setting software to assign message stop function to the Emergency Control Input terminals.
(Refer to the separate software instruction manual.)
6.3. Making Automatic Emergency Announcements Using Control Signal Inputs
(Automatic Fire Alarm Systems, etc.)
This function makes emergency broadcasts by playing back internal Alert or Evacuation announcements when
the emergency control input terminals located on the rear panel of the VM-3240VA, VM-3360VA, VM-3240E,
orVM-3360Ereceiveanemergencycontrolsignalfromaconnectedautomaticfirealarmsystemorexternal
equipment. These emergency announcements being broadcast can also be stopped by the control signal.
Performthefollowingsettingsinadvanceusingthesettingsoftware:
[Emergency control signal entry and operation]