3-20
Chapter 3
OPERATION
Failure output receiptstate indicator
Key ON/OFF indicator
Flashes yellow
Failure output receipt key
12
Yellow
5.3.RemoteMicrophone'sOperationExample
When the failure is detected, the buzzer built in the remote
microphone sounds, and the Zone 2F failure output receipt
state indicator flashes yellow.
Step 1. Press the Failure output receipt key (12) to
acknowledge the failure.
The buzzer stops sounding, and the Failure output
receipt state indicator switches from ashing to
steady on.
Step 2. Locate the cause, then remove it.
Connect a PC to the VX-3004F and read out the log data using the VX-3000 Setting Software.
For details, see the separate Setting Software Instructions, "MAINTENANCE."
Conrm the cause of failure or abnormality on the log data (in this example, the log data that the
speakerterminalforthezone2Fisopenstateislisted),thenxthefaultpart.
Note
Operation of failure indication differs depending on which the Failure indication setting is set to "Auto
reset" or "Manual reset" on the VX-3000 Setting Software.
[When set to "Auto reset"]
For most failure indications, the failure LED automatically goes off when the cause has been
corrected.Forcertainotherfailureindications,suchaspoweramplierfailureorspeakershorts,the
LED does not automatically go off. In such cases, Failure Output Reset key needs to be pressed.
[When set to "Manual reset"]
The failure indication is retained until the Failure output reset key is pressed even when failure is
restored.
Step 3. Press the Failure Output Reset key (4).
The Failure output receipt state indicator goes off.
Failure output reset indicator
Green
(The indicator lights only
when the key is pressed.)
Failure output receipt state indicator
Key ON/OFF indicator
Goes off
Failure Output Receipt keyFailure Output Reset key
4
12
Bekijk gratis de handleiding van Toa RM-210F, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Toa |
| Model | RM-210F |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 8488 MB |
Caratteristiche Prodotto
| Kleur van het product | Zwart |
| Gewicht | 350 g |
| Breedte | 110 mm |
| Diepte | 110 mm |
| Hoogte | 215 mm |