MIX 2 series RMG 8 T / RME 8 T actuators
5.2 Communication objects
The objects are divided into channel-related and common objects
The function of the objects depends on the selected channel function, i.e. switch or blinds
actuator.
5.2.1 Channel-related objects for the switch actuator
Table 4
No. Object name Function
Type
DPT
Flags
C
R
W
T
0
RMG 8 T channel C1 Switch object
1 bit
1,001
C R W -
RMG 8 T channel C1 Threshold 0..255
1 byte
5,010
C R W -
RMG 8 T channel C1 Threshold 0..65535
2 byte
7,001
C R W -
RMG 8 T channel C1 Threshold EIS 5 (DPT9.xxx)
2 byte
9.xxx
C R W -
RMG 8 T channel C1 Threshold as percent
1 byte
5,001
C R W -
1
RMG 8 T channel C1 Logic input in OR gate
1 bit
1,001
C R W -
RMG 8 T channel C1 Logic input in AND gate
1 bit
1,001
C R W -
RMG 8 T channel C1 Logic input in XOR gate
1 bit
1,001
C R W -
2 RMG 8 T channel C1 Lock
1 bit
1,003
C R W -
3 RMG 8 T channel C1 Call up/save scenes
1 byte
18,001
C R W T
4
RMG 8 T channel C1 Enable scenes = 1
1 bit
1,003
C R W -
RMG 8 T channel C1 Lock scenes = 1
1 bit
1,003
C R W -
5 RMG 8 T channel C1 Feedback On/Off
1 bit
1,001
C R - T
6
RMG 8 T channel C1 Operating hours feedback
2 byte
7,001
C R W T
RMG 8 T channel C1 Time to next service
2 byte
7,001
C R W T
7 RMG 8 T channel C1 Service required
1 bit
1,001
C R - T
8
RMG 8 T channel C1 Reset operating hours
1 bit
1,001
C R W -
RMG 8 T channel C1 Reset service
1 bit
1,001
C R W -
RMG 8 T channel C1 Switching with priority
2 bit
2,001
C R W -