MIX 2 series RMG 8 T / RME 8 T actuators
6.3.4 Important parameter settings
Standard or customer-defined parameter settings apply for unlisted parameters.
Table 40: TA 2
Parameter page
Parameters
Setting
Channel 1
Channel function
Switch/push button
Object type
Switching (1-bit)
Response to rising edge
On
Response to falling edge
Off
Table 41: RMG 8 T
Parameter page
Parameters
Setting
General
Type of basic module
RMG 8 T
Basic module: RMG 8 T
Channel C1 function
Switch actuator
RMG 8 T channel C1:
configuration options
Channel function
Flashing
Activation of function via
Switch object
Contact characteristics
Type of contact
NO contact
Flashing
ON phase:
Hours
0
Minutes
0
Seconds
1
OFF phase:
Hours
0
Minutes
0
Seconds
1
How often should it flash
Until it switches off
Version: May-14 (Subject to change) Page 75 of 87