MIX 2 series RMG 8 T / RME 8 T actuators
5.3.5.6 The "Staircase light with forewarning function .." parameter page
This parameter page appears if Staircase light with forewarning function is chosen as the
Channel function.
The user can, anytime, press a push button again, to extend the staircase light time.
Table 16
Designation
Values
Description
Staircase light time (min. 1 s)
hours (0..3)
0..3
Input of desired staircase light time in
hours.
minutes (0..60)
0..60
Input of desired staircase light time in
minutes.
seconds (0.255)
0..255
Default value = 1
Input of desired staircase light time in
seconds.
The maximum sum of
pulses 1..40
1..40
determines how long the staircase light
time can be extended by pressing the
button again.
Duration of
1st forewarning in s
(0..60)
0
The light switches off immediately once
the staircase light time is completed.
1..60
Default value = 10
Once the staircase light time is
completed, the light should briefly flash
and then stay on for the duration of the
forewarning
Duration of
2nd forewarning in s
(0..60)
0
No 2nd forewarning.
The light switches off at the end of the
1st forewarning.
1..60
Default value = 10
Second forewarning:
Once the 1st forewarning is completed,
the light should flash briefly and then
stay on for the duration of the 2nd
forewarning.
The light switches off when this time is
completed.
Example of forewarning function:
Staircase light time
Flashin
1st
forewarning
Flashin
g
2nd
forewarning
OFF
Version: May-14 (Subject to change) Page 42 of 87