MIX 2 series RMG 8 T / RME 8 T actuators
5.2.6 Description of common objects
Objects 78, 158, 238 "Manual"
Only available for devices in the MIX2 series (order number 493…)
Puts the relevant module in manual mode or sends the status of the manual operation.
Telegram
Meaning
Explanation
0 Auto
All channels can be operated via the bus as well as via the
buttons.
1 Manual
The channels can only be operated via the buttons on the device.
The safety telegrams are still being executed.
The duration of the manual mode, i.e. the Function of the manual button can be configured on
the General parameter page.
Objects 79, 159, 239 „RMG 8 T, EM1 RME 8 T, EM2 RME 8 T collective feedback
Only applies to switch actuator channels.
Sends the current switching status of the channels in a module as DPT 27.001.
Object 240 "Central permanent ON"
Central switch-on function.
Enables simultaneous switch on of all channels (basic and extension modules) with a single
telegram.
0 = No function
1 = Permanent ON
Participation in this object can be set individually for each channel (configuration options
parameter page).
IMPORTANT:
This object takes top priority.
As long as it is set, the other switch commands will not work on the participating channels.
Works on the following devices:
RMG 8 S/RME 8 S, RMG 4 I/RME 4 I, RMG 8 T*/RME 8 T*, RME 4 S/C-load,
DMG 2 T, DME 2 S/T, SME 2 S.
* Only applies to switch actuator channels