MIX 2 series RMG 8 T / RME 8 T actuators
5.2.2 Channel-related objects for the blinds actuator:
For the blinds function, 2 channels (e.g. C1+C5) are combined.
Therefore, the object numbers are not in consecutive order.
Table 6:
No. Object name Function
Type
DPT
Flags
C
R
W
T
0 RMG 8 T channel C1 UP/DOWN
1 bit
1,008
C R W -
1 RMG 8 T channel C1 Step/stop
1 bit
1,010
C R W -
2 RMG 8 T channel C1 % Height
1 byte
5,001
C R W -
3 RMG 8 T channel C1 % Slat
1 byte
5,001
C R W -
4 RMG 8 T channel C1 Lock comfort/automatic
1 bit
1,003
C R W -
5
RMG 8 T channel C1
1 = Lock
1 bit
1,003
C
R
W
-
RMG 8 T channel C1
1 = Release
C
R
W
-
6 RMG 8 T channel C1 Call up/save scenes
1 byte
18,001
C R W -
7
RMG 8 T channel C1
Enable scenes = 1
1 bit
1,003
C
R
W
-
RMG 8 T channel C1
Lock scenes = 1
C
R
W
-
8 RMG 8 T channel C1 Priority on safety
2 bit
2,003
C R W -
40 RMG 8 T channel C1 Position A
1 bit
1,003
C R W -
41 RMG 8 T channel C1 Position B
1 bit
1,003
C R W -
42 RMG 8 T channel C1 Position C
1 bit
1,003
C R W -
43 RMG 8 T channel C1 Height feedback
1 byte
5,001
C R - T
44 RMG 8 T channel C1 Slat feedback
1 byte
5,001
C R - T
Version: May-14 (Subject to change) Page 17 of 87