4.6.6.1 Threshold with Samples
The Threshold with Samples trigger uses
several measurements to decide when
toact.Thetriggercanbeconguredto
act quickly, or slowly, depending on the
number of measurement samples used.
A new sample is available every 50ms,
with the minimum samples being used
for a trigger being 1 sample, and the
maximum being 20 samples. Threshold
with Samples triggers are evaluated
every time a new sample is available.
Based on the below “New Trigger”
example below, the trigger will alarm
or turn on after 5 of any consecutive 10
samples are above 140V.
4.6.6.2 Autoping
The Autoping trigger uses a ping
commandonaperiodicbasisdenedin
thedevicesettingstotestifaspecicIP
address will respond. This trigger type is
useful if there is a problematic piece of
equipment that becomes unresponsive,
or if internet connectivity is inconsistent.
4.6.6.3 Schedule
The Schedule trigger uses the internal
time of the Axess ELITE+ to easily
congure single and recurring events
based on time. Only Alarm Actions are
used for this trigger.