4.6.6 Triggers Setup
TheTriggersSetuppageallowsforthemodicationofTriggers.Triggersdeneeventlogging
parametersandallowcongurationtoautomaticallycontrolandprotectconnectedequipment.
Triggers are categorized into four types, autoping, Threshold with Samples, Schedule, and
Contact Closure but all have the same possible actions. Actions can either be on the onset
(Trigger/Alarm Actions) or offset (Clear Actions) of a trigger. All Triggers are logged, along with
the associated actions.
TRIGGER TYPES
Item Description
Threshold with Samples
Uses measurements over an allotted time to take an action. This trigger type
iscongurabletoactveryquicklyorveryslowlydependingonenvironmental/
system needs.
Thresholds include:
• Line Voltage
• N-G Voltage
• Current
• Temperature (Axess Elite+ Internal temperature)
• External Temperature (I2C sensor temperature)
• Frequency
• Average Power
• Crest Factor
• Power Factor
Auto Ping
Issues a ping function on a periodic basis to determine if an IP asset is
accessible.
Schedule
Uses the device time to issue a one time or periodic command. We suggest
ensuring the NTP server is updating correctly to use the schedule trigger.
Contact Closure
The actions to be executed upon closing or opening of the contact closure
inputmaybedenedasvariousUserTriggersontheTriggersSetupweb
page.