Twelve types of events are logged:
▪ Overload: Load current draw has exceeded 25A
▪ Surge: enVision has been exposed to a transient voltage in one
of the 3 possible modes (between Live and Neutral, between
Live and Ground, between Neutral and Ground) with a peak
amplitude of 500V* or higher and a frequency of 20 kHz or
higher. *500V surge voltage amplitude applies to IEEE C62.41
Category B Impulse; surge voltage amplitudes necessary for
detection of other surge types may vary.
▪ Over Voltage (Cutoff): Line voltage exceeded the over voltage
shutdown threshold, and connected equipment was turned off.
▪ Over Voltage (Record): Line voltage exceeded the over voltage
record threshold, and connected equipment was not turned off.
▪ Under Voltage (Record): Line voltage dropped below the under
voltage record threshold, and connected equipment was not
turned off.
▪ Under Voltage (Cutoff): Line voltage dropped below the under
voltage shutdown threshold, and connected equipment was
turned off.
▪ Power Outage: Loss of AC power.
▪ Turn On: The enVision outlets were turned on.
▪ Turn Off (Cycle): A power cycle was initiated by a
received command.
▪ Turn Off (Software): Outlets were turned off by a received
command.
▪ Turn Off (Button): Outlets were turned off by the
pushbuttons.
▪ Turn Off (Loss of Ground): Outlets were turned off due to the
loss of the safety ground conductor at the wall receptacle.