14.
Specifications
Parameter
Specification
Load Rating
15/20 Amps at 120 Volts (SX-AX15E / SX-AX20E)
Power Requirement (no load)
5 Watts
Surge Let-through Voltage (6000 Volt Surge)
0 Volts
UL 1449 Adjunct Classification Test Results
1000 Surges, 6000 Volts, 3000 Amps, B3 pulse; measured
suppressed voltage, 170 Volts; no failures
Maximum Applied Surge Voltage
6000 Volts *
Maximum Applied Surge Current
Unlimited (due to current limiting) *
Maximum Applied Surge Energy
Unlimited (due to current limiting) *
Endurance (C62.41-1991 category B3 pulses)
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000
EMI/RFI Filter
Normal mode (50Ω load)
40 dB@100 KHz, 50dB@300 KHz, 50 dB@3 MHz, 50 dB@30 MHz
Common Mode (50Ω load)
18dB@300 KHz, 30 dB@1 MHz, 50 dB@5 MHz, 50 dB@20 MHz
Under-Voltage Auto Shutdown
Adjustable from 80V to 110V, or disabled.
Over-Voltage Auto Shutdown
Adjustable from 130V to 160V
Over-Current Auto Shutdown
Adjustable from 1A to 20A, or disabled.
Over-Temperature Auto Shutdown
Adjustable from 70 to 100°F, or disabled.
Measurement Accuracy
Voltage
± 1% from 90 – 160 VRMS
Current
± 1% from 0.1 – 20 ARMS (Resistive)
Power
± 5% from 0.1 – 2400 WRMS (Resistive)
Energy
± 5% kWh
Temperature
± 5.3C from -25 – 105C
Network Port
10/100 Ethernet connection on Female RJ-45, Auto Negotiating with
10/100/1000 network connections with Link and Activity LEDs
Serial Port
RS-232 on Female 9-pin D-subminiature, DCE
Temperature Sensor Input
2 x screw terminal
Auxiliary Relay Outputs
(2) 3 x screw terminal
Contact Closure Input
2 x screw terminal
Dimensions
19” W x 12.25” D x 1.75” H (Single Rack Space)
Weight
13 lb.
Temperature Range:
5C to 35C
Humidity Range
0% to 95% R.H. Non-condensing
Agency Listings
ETL Certified to UL 1449 3
rd
Edition
ETL Certified to UL 1283 5
th
Edition
ETL Certified to CSA 22.2 No. 8-M1986 (R2008)
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
*CAUTION: Do not install this device if there is not at least 10 meters (30 feet) or more between the electrical outlet and the electrical service panel.