Reconnection can be performed via remote access to the AFPE after interruption.
You can log in to iSolarCloud remotely. Then, find the target plant and choose Set-
tings; select the device, and choose Advanced Settings→ Power Control→ Clear
AFCI Alarm. After clearing the fault alarm, restart the device.
3 Automatic reconnection
Reconnection can be performed automatically after arc interruption.
Rule: Upon detecting a real arc fault, the device will report a fault and shut down.
Within the day, for the 1st to 4th arc fault alarm, the device will shut down for 10 mi-
nutes, then the alarm will be cleared and the device will restart; when the 5th or more
arc fault is reported, the device will shut down and not resume operation on that day.
In the event of the 1st to 4th arc fault alarm, ARM is powered off and restarted, and
the device can restart and reconnect to the grid normally, with the fault count reset to
"0". When the 5th arc fault is detected, if ARM is powered off and restarted due to ex-
ternal environment factors, the device will report a fault and shut down, with the fault
count changing to "1"; after 10 minutes, the fault alarm will be cleared and the device
will restart. If ARM is not powered off when the 5th or more arc fault is reported, you
need to clear the fault manually to get the device restarted and reconnected to the
grid normally; in this case, the fault count will be reset to "0". Or you can wait for the
fault to be cleared automatically the next day, in which case the fault count will
change to "1". See "Manual reconnection" and "Remote manual reconnection" for in-
structions on how to clear the fault alarm manually.
• AFCI protection configuration.
The AFCI configuration of each inverter model is shown in the table below.
Model SG3.0RS-L SG4.0/5.0/6.0RS-L
Classification F-I-AFPE-1–1–1 F-I-AFPE-1–1/1–2
Number of monitored strings per
input port
1
Number of input ports per
channel
1
Number of monitored channels 1 2
Rated channel current 16
Maximum current per input port
16
Rated interruption current
16
The fault arc detection function meets the standard requirements, please test
under the working conditions as required by the standard.