5 Electrical Connection User Manual
5.6.2 Requirements for OT/DT Terminal
OT/DT terminals (not included in the delivery scope) are required for fixing AC cables to the
terminal block. Purchase the OT/DT terminals according to the following requirements.
OT/DT Terminals of Phase Wire
• Specification: M12
OT/DT Terminal of PE Wire
• Specification: M12
5.6.3 Connection Procedure
This section introduces the connection steps with four-core cable as an example,
and the wiring method for three-core cable is the same.
step 1 Disconnect the AC-side circuit breaker and prevent it from inadvertent reconnection.
step 2 Loosen the two screws on the front cover of the junction box with the hexagon socket wrench
provided. Open the junction box. During the wiring process, the limit rod attached to the cover
keeps the junction box open.
52