User Manual 5 Electrical Connection
step 3 Apply paint to the grounding terminal to ensure corrosion resistance.
The grounding screws have been anchored to the side of the inverter before delivery,
and do not need to be prepared.
There are two grounding terminals. Use one of them to ground the inverter.
- - End
5.6 AC Cable Connection
5.6.1 AC Side Requirements
Only with the permission of the local grid department, the inverter can be connected
to the grid.
Before connecting the inverter to the grid, ensure the grid voltage and frequency comply with
requirements, for which, refer to "Technical Data". Otherwise, contact the electric power com
pany for help.
AC Circuit Breaker
WARNING
Over-current protection devices, such as AC circuit breakers and fuses, must be in
stalled on the AC side of the inverter and the grid side to ensure safe disconnection
between the inverter and the grid.
• Do not connect any local load between the inverter and the AC circuit breaker
except for the tracking axis.
• Multiple inverters cannot share one AC circuit breaker.
Multiple Inverters in Parallel Connection
When multiple inverters are connected to the grid in parallel, ensure that the maximum number
of inverters connected in parallel to a single winding of the box-type substation is 15. Otherwise,
please contact SUNGROW for technical scheme.
MV Transformer
The MV transformer used together with the inverter should meet the following requirements:
49