ACB specification 4000 A / 800 Vac / 3P, 2 pcs
Disconnector specification 260 A / 800 Vac / 3P, 28 pcs
Fuse specification
400A / 800 Vac / 1P, 84 pcs
350A / 800 Vac / 1P, 84 pcs
Protection
AC input protection FUSE+Disconnector
Transformer protection Oil-temperature, oil-level, oil-pressure
Relay protection 50 / 51,50N / 51N
LV overvoltage protection AC Type II (optional: AC Type I + II)
General Data
Dimensions(WxHxD) 6,058x2,896x2,438 mm
Approximate weight 24 T
Operating ambient temperature range
-20 to 60 (optional: -30 to 60
)
Auxiliary power supply 5 kVA / 400 V (optional: max. 40 kVA)
Degree of protection IP54
Allowable relative humidity range (non-
condensing)
0 – 95 %
Operating altitude 1000 m (standard) / > 1000 m (optional)
Communication
Standard: RS485, Ethernet; Optional:
optical fiber
Compliance
IEC 60076, IEC 62271-200, IEC
62271-202, IEC 61439-1, EN50588-1
MVS9000–LV
Transformer
Transformer type Oil immersed
Rated power 9000 kVA @ 51 ℃,9054 kVA @ 50
Max. power 10560 kVA @ 30
System Manual10 Appendix