Step 6 Close the load switch of the fault branch
Step 7 Place the door limit bracket at the initial position and lock the door.
Step 8 Power on the MV Station again.
--End
9.7 Replace the Fans of LV Cabinet
This section gives instructions on how to replace the fans.
Replace the upper centrifugal fan
1. Open the front door of the LV cabinet, unscrew the eight M5 fixing bolts on the air baffle,
and take down the air baffle.
2. Unscrew the four M5 fixing bolts on the fan.
3. Disconnect the wiring terminals, and take out the fan.
4. Install the new fan into the LV cabinet, by completing the above steps in reverse.
Replace the bottom centrifugal fan
1. Open the front door of the LV cabinet, Unscrew the eight M5 fixing bolts on the lower
sealing plate, and take down the lower sealing plate.
2. Unscrew the four M5 fixing bolts on the fan.
3. Disconnect the wiring terminals, and take out the fan.
4. Install the new fan into the LV cabinet, by completing the above steps in reverse.
System Manual 9 Routine Maintenance
79