7 Powering up and Powering down
NOTICE
The operations described in this chapter must be performed by professional personnel in
accordance with local regulations/standards.
7.1 Operation before Power on
7.1.1 Adjusting De-energized Tap Changer
Adjust the output voltage of the transformer. When operating the de-energized tap changer,
ensure that the transformer is in a non-excitation state, that is, the high and low voltage
sides of the transformer are uncharged.
When the voltage on the LV side remains unchanged, the output voltage on the HV side
under different gears is:
Gear
Output Voltage
1 (A) Standard voltage x 1.05
2 (B) Standard voltage x 1.025
3 (C) Standard voltage x 1.0
4 (D) Standard voltage x 0.975
5 (E) Standard voltage x 0.95
Take adjusting to gear 1 as an example, operate the de-energized tap changer as follows.
53