Operating altitude
1000 m (standard) / > 1000 m
(optional)
Communication
Standard: RS485, Ethernet, Optical
fiber
Compliance
IEC 60076, IEC 62271-200, IEC
62271-202, IEC 61439-1, EN50588-1
*Parameters may vary subject to specific project requirement.
10.2 Tightening Torques
To avoid poor contact caused by the loosening of copper cable lugs due to stress, and to
prevent heat or even fire due to increased contact resistance, make sure to tighten the
screws on the cable lugs at the recommended torques:
Bolt
Torque(N·m) Bolt Torque(N·m)
M3 0.7–1 M8 18–23
M4 1.8–2.4 M10 34–40
M5 4–4.8 M12 60–70
M6 7–8 M16 119–140
*Torque values listed in the table are intended for the bolt and nut assembly, and do not
apply to riveted nuts or riveted screws, etc. The torque to be adopted should depend on the
actual situation.
**Secure the cable at a proper point to reduce the stress on the cable lug.
10.3 Quality Assurance
When product faults occur during the warranty period, SUNGROW will provide free service
or replace the product with a new one.
Evidence
During the warranty period, the customer shall provide the product purchase invoice and
date. In addition, the trademark on the product shall be undamaged and legible. Otherwise,
SUNGROW has the right to refuse to honor the quality guarantee.
Conditions
• After replacement, unqualified products shall be processed by SUNGROW.
• The customer shall give SUNGROW a reasonable period to repair the faulty device.
System Manual10 Appendix
90