Sungrow MVS4500-LV handleiding
Handleiding
Je bekijkt pagina 94 van 97

Impedance 8% (±10%)
Oil type Mineral oil (PCB free)
Winding material Al / Al
Insulation class A
MV Switchgear
Insulation type SF6
Rate voltage 12 – 36 kV
Rate current 630 A
Internal arcing fault IAC AFL 20kA/1s
Qty.of feeder 3 feeders
LV Panel
Main switch specification 4000 A / 800 Vac / 3P, 1 pcs
Disconnector specification 260 A / 800 Vac / 3P, 15 pcs
Fuse specification
400A / 800 Vac / 1P, 45 pcs
350A / 800 Vac / 1P, 45 pcs(optional)
Protection
AC input protection FUSE+Disconnector
Transformer protection Oil-temperature, oil-level, oil-pressure
Relay protection 50 / 51,50N / 51N
LV overvoltage protection AC Type II (optional: AC Type I + II)
General Data
Dimensions(WxHxD)* 6,058x2,896x2,438 mm
Approximate weight* 19 T
Operating ambient temperature range -30 ℃ to 60 ℃
Auxiliary power supply 5 kVA / 400 V (optional: max. 40 kVA)
Degree of protection IP54
Allowable relative humidity range (non-
condensing)
0 – 95 %
System Manual 10 Appendix
89
Bekijk gratis de handleiding van Sungrow MVS4500-LV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Sungrow |
| Model | MVS4500-LV |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9056 MB |