Relay protection 50 / 51,50N / 51N
LV overvoltage protection AC Type II (optional: AC Type I + II)
General Data
Dimensions(WxHxD)* 6,058x2,896x2,438 mm
Approximate weight* 15 T
Operating ambient temperature range -20 to 60 (optional: -30 to 60 )
Auxiliary power supply 5 kVA / 400 V (optional: max. 40 kVA)
Degree of protection IP54
Allowable relative humidity range (non-
condensing)
0 – 95 %
Operating altitude 1000 m (standard) / > 1000 m (optional)
Communication
Standard: RS485, Ethernet; Optional:
optical fiber
Compliance
IEC 60076, IEC 62271-200, IEC
62271-202, IEC 61439-1, EN50588-1
*Parameters may vary subject to specific project requirement.
MVS4500–LV
Transformer
Transformer type Oil immersed
Rated power 4500 kVA @ 51
Max. power 5250 kVA @ 30
Vector group Dy11
MV / LV voltage 0.8 kV / 12 kV – 36 kV
Maximum input current at nominal voltage 3811 A
Frequency 50 Hz / 60 Hz
Tapping on HV 0, ±2×2.5%
Efficiency ≥99%
Cooling type ONAN (Oil Natural Air Natural)