Transformer MVS3200–LV MVS4480–LV
LV Panel
Main switch specification 4000 A / 800 Vac / 3P, 1 pcs
Disconnector specification
260 A / 800 Vac / 3P, 10
pcs
260 A / 800 Vac / 3P, 14
pcs
Fuse specification
400A / 800 Vac / 1P, 30
pcs
350A / 800 Vac / 1P, 30
pcs(optional)
400A / 800 Vac / 1P, 42
pcs
350A / 800 Vac / 1P, 42
pcs(optional)
Protection
AC input protection FUSE+Disconnector
Transformer protection Oil-temperature, oil-level, oil-pressure
Relay protection 50 / 51,50N / 51N
LV overvoltage protection AC Type II (optional: AC Type I + II)
General Data
Dimensions(WxHxD)* 6,058x2,896x2,438 mm
Approximate weight* 15 T 17 T
Operating ambient
temperature range
-20 to 60 (optional: -30 to 60 )
Auxiliary power supply 5 kVA / 400 V (optional: max. 40 kVA)
Degree of protection IP54
Allowable relative humidity
range (non-condensing)
0 – 95 %
Operating altitude 1000 m (standard) / > 1000 m (optional)
Communication Standard: RS485, Ethernet; Optional: optical fiber
Compliance
IEC 60076, IEC 62271-200, IEC 62271-202, IEC
61439-1, EN50588-1
*Parameters may vary subject to specific project requirement.