Sungrow MVS4500-LV handleiding
Handleiding
Je bekijkt pagina 76 van 97

Check Item Check Method
Check whether warning labels are clear and replace them if
necessary.
Check whether the humidity and dust in the equipment are heavy,
and clean the equipment.
Check whether the surface of the container has been corroded. If
so, repaint the corroded area by referring to9.5 Appearance
Repair
MV switchgear
Check the SF6 air pressure meter to see whether the pointer is in
the green range. If the pointer is close to red, stop running it in
time and supply it with gas.
Check the electric indicator to see whether theL1/L2/L3 indicator
is normal. If not, replace theL1/L2/L3 indicator under power off
condition.
LV cabinet
Check whether the surge protection device indicator is normal
(green) or faulty (red).
Check whether there is condensation on the internal side panel
and top cover.
Table 9-5 Maintenance (If necessary)
Check Item Check Method
Other equipment
Replace the damaged lights in time.
Replace the damaged smoke sensor and fire extinguisher in
time.
Replace the temperature and humidity controller in time.
Device
maintenance
For the maintenance of various equipment inside, refer to the
related manuals.
WARNING
Before performing maintenance, remove the internal protective grid. Make sure to
reassembly the grid and fasten all the screws after the maintenance work.
Make sure all bolts are securely fixed.
WARNING
Repair immediately any anomalies found during routine maintenance. If there are any
doubts, contact Sungrow.
System Manual 9 Routine Maintenance
71