Sungrow MVS4500-LV handleiding

97 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 59 van 97
6.9 Checking after Electrical Connection
Checking Item Requirement
Equipment
appearance
The equipment is intact, and free from rust and paint flake-
off. Repaint areas with paint flake-off (if any).
The labels on the equipment are legible.
The damaged labels must be replaced in time.
Appearance of cable
Cable sheathings are properly wrapped and free from
obvious damage.
Hoses that contain cables are intact.
Cable connection
Cables are connected in the designed positions.
Terminals are prepared as required and securely connected.
Labels on both ends of each cable are clear and specific,
and attached in the same direction.
Cable routing
Power cables and communication cables must be routed
separately.
Cables are neat and tidy.
The joints of cable ties are evenly cut without burrs.
Cables are placed properly and not tense at turning points.
Cable routes are straight and smooth, and do not intersect
inside a cabinet.
Container
The container is clean and tidy inside, without any
unnecessary cables, cable heads, terminals, or tools. No
obvious garbage is found outside the equipment.
Clean up the dust and sandstorms inside the container.
System Manual6 Electrical Installation
54

Bekijk gratis de handleiding van Sungrow MVS4500-LV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSungrow
ModelMVS4500-LV
CategorieNiet gecategoriseerd
TaalNederlands
Grootte9056 MB