Figure Name Description
Oil Temperature
Indicator
The alarm temperature is set to 95. When
the oil temperature reaches the value, alarm
signals will be sent to the intelligent power
distribution cabinet or a communication unit
provided by the customer.
The tripping temperature is set to 100.
When the oil temperature reaches the value,
tripping signals will be sent to the intelligent
power distribution cabinet or a communication
unit provided by the customer. At the same
time, the transformer will be disconnected
from the upstream and downstream devices.
Oil drain valve
Open the valve for oil drainage when the oil
level is excessively high or when operations
such as maintenance are required.
Tap changer
The tap changer has five tap positions: 1, 2 ,
3, 4 , 5. For more details, refer to 7.1.1
Adjusting De-energized Tap Changer
Parameters marked with a) and b) are factory default values and can be adjusted
according to actual condition.
3.4.3 MV Switchgear
The MVswitchgear consists of load switch cabinet, circuit breaker cabinet, and direct cable
connection cabinet.
Names of the cabinets vary with MV switchgear manufacturers.
For example, the appearance of the CCV cabinet of Siemens is as follows:
System Manual 3 Product Description
15