Structural Concepts Oasis BD3632 handleiding
Handleiding
Je bekijkt pagina 22 van 25

22
CONDITION TROUBLESHOOTING
Low Suction
Pressure
Check if sight glass (if present) is flashing or showing low charge.
Check that expansion valve (TXV) isn’t restricted. Check element charge.
Check that liquid line or filter isn’t restricted. Check that refrigeration line / courtesy
loop is not kinked.
Check that evaporator fan motor is working.
Check that superheat is between 6 °F to 8 °F (-14 °C to -13 °C).
Check that there is no air recirculation around evaporator coil.
Check that evaporator coil is not iced up.
High Suction
Pressure
Check that the “cooling load” isn’t high. Product must be pre-chilled before placing
in refrigerated section of case.
Check that case is at least 15-feet from exterior doors, overhead HVAC vents or
any air curtain disruption.
Check that unit is not exposed to direct sunlight via windows or any other heat
source (ovens, fryers, etc.).
Check that superheat adjustment isn’t low.
Check TXV bulb installation
a. Poor thermal contact.
b. Warm location.
TROUBLESHOOTING - R-290 EVAPORATOR SYSTEM (BY TRAINED SERVICE PROVIDERS ONLY)
Bekijk gratis de handleiding van Structural Concepts Oasis BD3632, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Structural Concepts |
Model | Oasis BD3632 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 8246 MB |