Structural Concepts Fusion GMDSV12R handleiding
Handleiding
Je bekijkt pagina 16 van 32

Fusion® User Manual 16
Overview
These instructions apply to models only with the Atmosphere system included. These models are GMDSV4RA, GMDSVX4RA,
GMDSV6RA, GMDSV8A, GMDSV12RA.
System Requirements
System Overview:
The Atmosphere system is designed to maintain a steady relative humidity for a meat/ cheese/ seafood case. This system has
a “closed” design so there are no reservoirs to be cleaned.
Electrical:
Rating: 120VAC 60Hz 25A
Requirements: 120V 60Hz 15A single gang outlet wired onsite.
The outlet must be located within 5 feet of control enclosure should be on the case itself.
Plumbing:
1/2NPTF potable cold-water supply with ¼ in OD tube connector
Nearby drain or condensate pump required.
Water must be ltered through a reverse osmosis water lter with a TDS range of 7ppm-15ppm. One can be purchased
with the unit or previously installed in the store.
Atmosphere System Requirements and
Operation
Bekijk gratis de handleiding van Structural Concepts Fusion GMDSV12R, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Structural Concepts |
Model | Fusion GMDSV12R |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 6215 MB |