Fusion® User Manual 16
Overview
These instructions apply to models only with the Atmosphere system included. These models are GMDSV4RA, GMDSVX4RA,
GMDSV6RA, GMDSV8A, GMDSV12RA.
System Requirements
System Overview:
The Atmosphere system is designed to maintain a steady relative humidity for a meat/ cheese/ seafood case. This system has
a “closed” design so there are no reservoirs to be cleaned.
Electrical:
Rating: 120VAC 60Hz 25A
Requirements: 120V 60Hz 15A single gang outlet wired onsite.
The outlet must be located within 5 feet of control enclosure should be on the case itself.
Plumbing:
1/2NPTF potable cold-water supply with ¼ in OD tube connector
Nearby drain or condensate pump required.
Water must be ltered through a reverse osmosis water lter with a TDS range of 7ppm-15ppm. One can be purchased
with the unit or previously installed in the store.
Atmosphere System Requirements and
Operation