CONDITION TROUBLESHOOTING
Low Suction
Pressure
If sight glass is part of condensing unit, check if it is flashing or showing low charge.
Check that expansion valve (TXV) isnt restricted. Check element charge.
Check that liquid line or filter isnt restricted. Check that refrigeration line / courtesy
loop is not kinked.
Check that evaporator fan motor is working.
Check that superheat is between 6 °F to 8 °F.
Check that there is no air recirculation around evaporator coil.
Check that evaporator coil is not iced up.
High Suction
Pressure
Check that the cooling loadisnt high. Product must be pre-chilled before placing in
refrigerated section of case.
Check that case is at least 15-feet from exterior doors, overhead HVAC vents or any
air curtain disruption.
Check that unit is not exposed to direct sunlight via windows or any other heat source
(ovens, fryers, etc.).
Check that superheat adjustment isnt low.
Check TXV bulb installation
a. Poor thermal contact.
b. Warm location.
TROUBLESHOOTING - R-290 EVAPORATOR SYSTEM (BY TRAINED SERVICE PROVIDERS ONLY)